Conventional Fire Panels |
The FI/C range of conventional fire control panels feature 3 models with 2, 4 and 8 zones. Housed in a stylish modern ABS housing, the FI/C range of fire panels are ideal for small to medium sized installations.
| FireBrand 2/4/8 Zone | |
![]() |
The FI/C range of conventional fire control panels features three models with 2, 4, and 8 zones. Housed in a stylish modern ABS housing, the FI/C range of fire panels are ideal for small to medium size installations.Designed and manufactured to comply with the requirements of EN54 parts 2 and 4 (1998) the FI/C uses active end of line monitoring to permit head removal protection as required by BS5839. Programmable zone coincidence and alarm delay timer (0-10 min) are standard features to help reduce false alarms. The one man test facility enables simple and rapid testing of the system at commissioning and during maintenance operation. |
| Firebrand Conventional Panel | |
| Firebrand Sales Sheet | |
- Conventional Fire Panels 2/4/8 - Technical Data & Features
-
TECHNICAL DATA Up to 20 conventional smoke and/or heat detectors per zone. Active End of Line monitoring Programmable non-latching zones Delay timer programmable on/off per zone Zone coincidence programmable for adjacent zones One man test Supervised auxiliary 24 volt output 2 supervised/ monitored sounder circuit 2 programmable inputs for Class change, remote silence, remote reset etc 2 Relay outputs fire and fault,Power supply 1,5A at 28Vdc Fully EN54 part 2 and 4 compliant FEATURES • Two, four and eight zone non-expandable control panels
• Up to 32 conventional smoke and/or heat detectors per zone (not exceeding 2000 sq metres per zone)
• Active end of line monitoring
• Programmable non-latching zones
• Delay timer programmable on/off per zones
• Zone coincidence programmable for adjacent zones
• Two access levels
• One man test
• Supervised auxiliary 24 volt output
• 2 Supervised/monitored sounder circuits
• 2 Programmable inputs for class change, remote silence, remote reset etc.
• 2 Relay outputs, fire and fault
• Power supply 1.5A at 28Vdc
• Fully EN54 part 2 and 4 compliant
• Repeater output
• Multiplexed output for LED’s and additional relay outputs per zone
• Addressable Loop interface card
| FireBrand Repeaters | |
![]() |
The repeater panels, two models FI/C/REP and FI/C/MREP will provide remote control and system display status for our range of conventional fire panels. It is available both as a Mini-Repeater and in the standard FI/C enclosure It includes a standard RS-232. The unit is also compatible with all of the FireBrand data loop interfaces: RS-485, Fibre Optics and TCP/IP. Power for the repeater can be supplied from the control panels auxiliary power output or an external 24 volt power supply |