Conventional Fire Panels

 Conventional Fire Panels

The FI/C range of conventional fire control panels feature 3 models with 2, 4 and 8 zones. Housed in a stylish modern ABS housing, the FI/C range of fire panels are ideal for small to medium sized installations.

FireBrand 2/4/8 Zone
 Firebrand 2/4/8 Zone The FI/C range of conventional fire control panels features three models with 2, 4, and 8 zones. Housed in a stylish modern ABS housing, the FI/C range of fire panels are ideal for small to medium size installations.Designed and manufactured to comply with the requirements of EN54 parts 2 and 4 (1998) the FI/C uses active end of line monitoring to permit head removal protection as required by BS5839.

Programmable zone coincidence and alarm delay timer (0-10 min) are standard features to help reduce false alarms.
The one man test facility enables simple and rapid testing of the system at commissioning and during maintenance operation. 
Firebrand Conventional Panel
Firebrand Sales Sheet

Conventional Fire Panels 2/4/8 - Technical Data & Features
TECHNICAL DATA
Up to 20 conventional smoke and/or heat detectors per zone. 
Active End of Line monitoring 
Programmable non-latching zones 
Delay timer programmable on/off per zone 
Zone coincidence programmable for adjacent zones 
One man test 
Supervised auxiliary 24 volt output 
2 supervised/ monitored sounder circuit 
2 programmable inputs for Class change, remote silence, remote reset etc 
2 Relay outputs fire and fault,Power supply 1,5A at 28Vdc 
Fully EN54 part 2 and 4 compliant 
FEATURES
• Two, four and eight zone non-expandable control panels
• Up to 32 conventional smoke and/or heat detectors per zone (not exceeding 2000 sq metres per zone)
• Active end of line monitoring
• Programmable non-latching zones
• Delay timer programmable on/off per zones
• Zone coincidence programmable for adjacent zones
• Two access levels
• One man test
• Supervised auxiliary 24 volt output
• 2 Supervised/monitored sounder circuits
• 2 Programmable inputs for class change, remote silence, remote reset etc.
• 2 Relay outputs, fire and fault
• Power supply 1.5A at 28Vdc
• Fully EN54 part 2 and 4 compliant
• Repeater output
• Multiplexed output for LED’s and additional relay outputs per zone
• Addressable Loop interface card 

FireBrand Repeaters 
 FI C Repeater The repeater panels, two models FI/C/REP and FI/C/MREP will provide remote control and system display status for our range of conventional fire panels. It is available both as a Mini-Repeater and in the standard FI/C enclosure

It includes a standard RS-232. The unit is also compatible with all of the FireBrand data loop interfaces: RS-485, Fibre Optics and TCP/IP. Power for the repeater can be supplied from the control panels auxiliary power output or an external 24 volt power supply   
Firebrand Repeater
Firebrand Sales Sheet